Load calculation guide

Cooling Load Calculation Explained

Cooling load is more than outdoor temperature: it includes sensible heat and moisture from the building, people, equipment, and outdoor air.

Created · Updated

Separate sensible and latent load

Sensible load changes dry-bulb temperature. Latent load is associated with moisture removal. A space can have a modest sensible total but still need meaningful dehumidification capacity because of people or humid outdoor air.

Where cooling gains come from

GainWhat changes itCheck
EnvelopeU-values, area, outdoor conditionsConstruction and design temperature
Solar through glassOrientation, SHGC, shade, timeGlazing data and exposure
InternalPeople, lights, equipment, scheduleActual watts and occupancy
Outdoor airVentilation, infiltration, humidityAirflow and psychrometric conditions

Useful calculation checks

Electrical input can be converted at 1 W = 3.412141633 BTU/h. For a preliminary sensible outdoor-air check in U.S. customary units, 1.08 × CFM × dry-bulb temperature difference estimates the sensible rate. Neither shortcut captures latent load or the hourly solar-storage behavior used in detailed methods.

Example

A 300 W lighting load contributes about 1,024 BTU/h before schedule and heat-to-space assumptions. If 100 CFM of outdoor air is 20°F warmer than indoors, the preliminary sensible outdoor-air term is 2,160 BTU/h. Both values must be combined with the relevant building and moisture inputs.

Decision rule

Use a detailed calculation when selecting equipment, when humidity matters, when solar exposure is significant, or when rooms have different exposures. A square-foot rate is only a comparison value.

Related tools