Heat Pump Efficiency Ratings Reference

Use the correct metric for the question: point performance, cooling efficiency, or seasonal heating and cooling comparison.

Created · Updated

Efficiency metric lookup

MetricDefinitionUnitsUse it for
COPUseful heating or cooling effect divided by net work input, expressed in identical units.DimensionlessA documented point condition or measured interval.
EERAverage rate of space cooling delivered divided by average electrical energy consumed.BTU/WhA stated cooling rating condition.
SEER2Seasonal cooling efficiency determined by the current prescribed test method.Seasonal BTU/Wh ratingComparing certified equipment; not a point COP.
HSPF2Total seasonal space heating required in the specified test climate divided by total electrical energy consumed.Seasonal BTU/Wh ratingComparing certified heating performance; not a point COP.

Matched-condition conversion

EER (BTU/Wh) = COP × 3.412141633
COP = EER ÷ 3.412141633

This conversion is valid only when COP and EER describe the same cooling output and electrical input boundary at the same condition. It does not convert a seasonal rating to a point COP, or predict annual cost.

How to identify the right value

  1. State whether the question is heating or cooling and whether it concerns a moment, a measured interval, or a whole season.
  2. Keep load, equipment data, and runtime at the same operating condition.
  3. Use COP for the operating-cost calculator only when it comes from a matching condition.
  4. Keep SEER2 and HSPF2 as their certified seasonal ratings unless an official model provides the appropriate conversion method.

Example

A cooling COP of 3.00 at a given test point corresponds to EER 10.24 BTU/Wh at that same point (3.00 × 3.412141633). It does not mean the unit has a SEER2 of 10.24, because SEER2 is a seasonal test metric.

Limits and next steps

Efficiency labels do not establish whether the equipment has enough capacity at a design condition, whether an electrical circuit is adequate, or how a particular building will operate. Verify the system's certified combination and manufacturer performance data, then use an appropriate load calculation and qualified design process.

Related resources

Sources and scope

Definitions are summarized from DOE material. Rating metrics depend on equipment category and test procedure; use the governing program and manufacturer documentation for product decisions.