Load calculation guide

Heating Load Calculation Explained

Heating load is the rate of heat input needed at the selected winter design condition, not a square-footage rule.

Created · Updated

Start with temperature difference

Conduction is driven by the difference between the indoor target and outdoor design temperature. Use the local design condition chosen for the project; do not mix weather data sources or apply a cooling condition to a heating calculation.

Document the heat-loss path

PathData neededWhy it matters
Walls, roof, floorArea and thermal performanceDetermines conductive heat loss
Windows and doorsArea, U-value, exposureCan dominate a small room
Infiltration and ventilationAirflow and temperature differenceAdds outdoor-air sensible loss
Internal gainsSchedule and reliabilityMay offset loss only when present

Useful check, not a complete method

For preliminary sensible outdoor-air heat loss in U.S. customary units, 1.08 × CFM × ΔT is a common check. For example, 100 CFM with a 30°F difference is 3,240 BTU/h. It does not replace a complete envelope, humidity, equipment, or distribution analysis.

Common mistakes

  • Counting lights or occupants as guaranteed heating capacity when schedules do not match the winter peak.
  • Ignoring the outside-air path because the building is described as “tight.”
  • Selecting a furnace or heat pump only from a BTU/h result without checking manufacturer performance at the design condition.

Related tools